ACL-7125
8 Channel Relay Actuator & Isolated D/I Card
AC/DC Polarity Free Inputs !!



Description

The ACL-7125 provides 8 electro-mechanical SPDT relays and 8 opto-isolated digital inputs on a compact board.

The 8 electro-mechanical relay outputs are addressed as a single I/O byte. Four of the relays are Form C contacts (normally open and normally closed) and the remaining relays are normally open. A red LED indicates each relay's ON/OFF status for monitoring.

The 8 opto-isolated D/I channels are used for sensing digital inputs and provide 1,000 VDC for isolation. Can be configured as filtered AC or non-filtered AC by jumper settings.

  Retour

Software

Two software tools support the ACL-7125.

An extensive library of functions is available that supports Microsoft C and Borland C/C++. Example programs are included to demonstrate how to write C programs for the ACL-7125.

The ACLS-DLL1 is a high performance Windows driver for digital I/O functions. It supplies a DLL that can be accessed from C, C++ and Visual Basic under the Windows 3.x environment.

  Retour

Features

  • 8 relay actuator outputs
  • 8 opto-isolated digital inputs
  • LED's indicate the energized relays
  • Jumper selectable inputs for AC/DC isolated input
  • On-board relay driving circuits
  • On-board digital input signal conditioning circuits
  • Fully compatible with ACL-725 and Advantech's PCL-725

  Retour


Specifications

Relay Outputs

  • Relay type : Single Pole, Double Throw (SPDT)
  • Contact rating : 120VAC @ 0.5 A or 30 VDC @ 1 A
  • Breakdown voltage : 300 V Peak AC/DC min.
  • Relay on/off time : 5 msec typical
  • Relay current : +12 V @ 33 mA for each relay

Isolated Inputs

  • Opto-isolator : PC-814
  • Input channels : 8
  • Input signal : Non-polarized AC or DC
  • Input voltage : 5~2 4VDC or AC, 50 ~ 1,000 Hz
  • Input impedance : 1.2 Kohm
  • Isolation voltage : 1,000 VDC channel-to-channel and channel-to-ground
  • Response time : 20 µsec without AC filter, 2.2 ms with AC filter

 

Physical, Environmental

  • Power consumption :
    +5 V @ 200 mA typical
    +12 V @ 270 mAmax, all relays energized

  Retour


Ordering Information

ACL-7125 : Relay Actuator & Isolated D/I Card

ACLD-9137 : Direct Screw Terminal Board

ACLS-DLL1 : Windows 3.x DLL Driver

Retour