ACLD-9182A/B
16-CH Opto-Isolated
Digital Input Termination Board
Isolation and Dry Contact / Non Polarized Opto Isolated !! |

Description
The ACLD-9182A/B opto-isolated D/I termination
board provides 16 optically isolated digital inputs for use with any ACL series I/O board
with D/I channels on 20-pin flat ribbon connectors.
Optical isolation provides a good solution in the
prevention of floating potential and ground loop problems.
Each input channel has a red LED to reflect the
input status. If the input voltage is high, the LED will light, otherwise the LED is off.
Each input channel is jumper selectable to be either AC-filter or non-AC-filter.
Non-Polarized, Opto-Isolated Digital Input
(ACLD-9128B only). The digital input is first routed through a photocoupler (PC-814), so
that the connections are not polarity sensitive whether used on AC or DC voltage. Also, a
single-pole filter with a time constant about 5ms is used to filter when the AC inputs
pass through. The outstanding features of this circuitry are:
- Non polarity sensitive digital input
- Both DC or AC (50~1000 Hz) inputs
- Up to 1,000 V isolation coltage
- DC noise rejection (spikes or constant debouncing)
Retour
Features
- 16 opto-isolated digital input channels
- For use with ACL DAS Card 20-pin digital input
connector
- AC or DC polarity free digital input
- On-board LEDs reflect the input logic status
- Built-in screw terminals for easy input wiring
- LEDs indicate status of relays
Retour
Specifications
- Input Range : 0~24 VDC
- Opto-isolator : PC-814
- Input channel : 16
- Input signal : 3~24 VDC
or AC , 50~1,000 Hz
- Input impedance : 1.2 Kohm
- Isolation voltage : 1,000 VDC channel-to-channel and channel-to-ground
- Response time: 20 ”sec without AC filter, 2.2 msec
with AC filter
- Connector : 20-pin flat ribbon cable connector
- Screw terminal: #22 to #12 AWG wires
|
ACLD-9128A |
ACLD-9128A |
| Input range |
0 ~ 24 VDC |
0 ~ 24 VDC |
| Input signal |
Threshold Voltage
1.5 VDC adjustable |
3 ~ 24 VDC or
AC (50 ~ 1,000 Hz) |
| Opto isolator |
4N 35 |
PC-814 |
| Input voltage |
DC only |
AC / DC |
| Input mode |
Isolation and dry contact |
Isolation |
Physical, Environmental
- Dimensions : 205 mm x 114.3 mm
- Operating temperature: 0 ~ 60șC
- Storage temperature : -20 ~ 80șC
- Humidity: 5~95%, non-condensing
Retour
Ordering Information
ACLD-9182A : 16 CH Isolation
/ Non Isolation D/I Termination Board
ACLD-9182B : 16 CH Isolation
AC/DC Termination Board
Retour |