ND-6013
3-channel RTD Input Module 


Specifications

Analog Input

  • Analog Input Type:Pt-100 or Ni RT
    RTD type Temperature Range
    Pt -100~+100°C=0.00385
    Pt 0~+100°C=0.00385
    Pt 0~+200°C=0.00385
    Pt 0~+600°C=0.00385
    Pt -100~+100°C=0.003916
    Pt 0~+100°C=0.003916
    Pt 0~+200°C=0.003916
    Pt 0~+600°C=0.003916
    Ni -80~+100°C
    Ni 0~+100°C
  • Isolation Voltage : 3000 VDC
  • Sampling Rate : 10 samples/sec
  • Bandwidth : 4 Hz
  • Input Wiring : 2, 3 or 4 wires
  • Accuracy : ±0.05%
  • Zero Drift : ±0.3 µV /°C
  • Span Drift : ±25 ppm/°C
  • CMR @ 50/60 Hz : 150 dB
  • NMR @ 50/60 Hz : 100 dB

Power

  • Power Requirements : unregulated +10 to +30 VDC
  • Power Consumption : 1.2 W
  • Internal switching regulator
  • Power reversal protection

Environmental

  • EMI : meets FCC class A
  • Operating : -10 to 60°C
  • Storage : -20 to 80°C
  • Humidity : 5~95%